QUINT POWER power supplies with maximum functionality
QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effective system protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states before errors occur.
Reliable starting of heavy loads takes place via the static power reserve POWER BOOST. Thanks to the adjustable voltage, all ranges between 5 V DC ... 56 V DC are covered.
AC operation |
Nominal input voltage range |
3x 400 V AC ... 500 V AC |
Input voltage range |
3x 400 V AC ... 500 V AC -20 % ... +15 % |
Voltage type of supply voltage |
AC/DC |
Inrush current |
< 15 A (at 25 °C) |
Inrush current integral (I2t) |
< 1 A2s |
Inrush current limitation |
15 A |
AC frequency range |
45 Hz ... 65 Hz |
Frequency range DC |
0 Hz |
Mains buffering time |
> 25 ms (400 V AC) |
> 35 ms (500 V AC) |
Current consumption |
3x 2.1 A (400 V AC) |
3x 1.5 A (500 V AC) |
Nominal power consumption |
1342 VA |
Protective circuit |
Transient surge protection; Varistor, gas-filled surge arrester |
Power factor (cos phi) |
0.76 |
Typical response time |
< 0.5 s |
Permissible backup fuse |
B6 B10 B16 AC: |
Permissible DC backup fuse |
DC: Connect a suitable fuse upstream |
Recommended breaker for input protection |
6 A ... 20 A (Characteristic B, C, D, K or comparable) |
Discharge current to PE |
< 3.5 mA |
DC operation |
Nominal input voltage range |
± 500 V DC ... 600 V DC |
Input voltage range |
500 V DC ... 600 V DC -10 % ... +34 % (mid-point earthed) |
Current consumption |
2.2 A (500 V DC) |
1.9 A (600 V DC) |
Recommended breaker for input protection |
1x 6 A ≥ 1000 V DC (10 x 38 mm, 30 kA L/R = 2 ms) |