QUINT POWER power supplies with maximum functionality
QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effective system protection. In addition, the high system availability is ensured by preventive function monitoring which reports critical operating states before errors can occur.
Reliable starting of heavy loads takes place via the static power reserve POWER BOOST. Thanks to the adjustable voltage, all ranges between 18 V DC ... 29.5 V DC are covered.
AC operation |
Nominal input voltage range |
100 V AC ... 240 V AC |
110 V DC ... 250 V DC |
Input voltage range |
85 V AC ... 264 V AC |
90 V DC ... 410 V DC +5 % (UL 508: ≤ 250 V DC) |
Input voltage range AC |
85 V AC ... 264 V AC |
Input voltage range DC |
90 V DC ... 410 V DC +5 % (UL 508: ≤ 250 V DC) |
Electric strength, max. |
300 V AC |
Voltage type of supply voltage |
AC/DC |
Inrush current |
< 15 A |
Inrush current integral (I2t) |
< 1 A2s |
AC frequency range |
50 Hz ... 60 Hz |
Mains buffering time |
typ. 55 ms (120 V AC) |
typ. 55 ms (230 V AC) |
Current consumption |
1.5 A (100 V AC) |
0.6 A (240 V AC) |
1.2 A (120 V AC) |
0.6 A (230 V AC) |
1.3 A (110 V DC) |
0.6 A (220 V DC) |
1.4 A (100 V DC) |
0.6 A (250 V DC) |
Nominal power consumption |
141 VA |
Protective circuit |
Transient surge protection; Varistor |
Typical response time |
< 0.15 s |
Input fuse |
5 A (slow-blow, internal) |
Permissible backup fuse |
B6 B10 B16 AC: |
Recommended breaker for input protection |
6 A ... 16 A (AC: Characteristics B, C, D, K) |
Discharge current to PE |
< 3.5 mA |